Model Flow Fan Latent* — BTU/hr Sensible — BTU/hr
# Rate Speed 25ºF 35ºF 45ºF 25ºF 35ºF 45ºF
HC 19-15 3 gpm Boost 6,430 10,638 15,488 5,239 6,263 7,157
Medium 6,080 10,035 14,588 4,774 5,806 6,719
Low 5,466 8,995 13,042 4,333 5,163 5,886
HC 14-10 3 gpm Boost 4,932 8,088 11,706 4,166 5,075 5,882
Medium 4,034 6,588 9,503 3,449 4,132 4,731
Low 3,359 5,485 7,853 2,934 3,608 4,211
HC 9-6 3 gpm Boost 2,662 4,314 6,187 2,169 3,013 3,849
Medium 2,218 3,585 5,132 1,961 2,324 2,638
Low 1,822 2,939 4,204 1,626 1,943 2,218
HC 6-4 3 gpm Boost 1,810 2,921 4,178 1,459 2,026 2.590
Medium 1,409 2,271 3,243 1,275 1,561 1,816
Low 1,147 1,845 2,633 1,047 1,300 1,527
Myson, Inc. • 800-698-9690 • www.MysonInc.com 9
MODEL UNIT WEIGHT
# WEIGHT PACKED
FAN CONVECTOR COMPARISON @ 180°F WATER TEMP
FRICTION LOSS
(HEAD)
UNIT WEIGHT
(LBS)
HC 19-15 Boost/Med/Low 41/33/26 ft 95/77/61 sq ft
HC 14-10 Boost/Med/Low 33/27/23 ft 78/64/53 sq ft
HC 9-6 Boost/Med/Low 22/20/17 ft 51/46/40 sq ft
HC 6-4 Boost/Med/Low 13/11/10 ft 31/26/22 sq ft
MODEL FT WG
# 0.5 GPM 1.25 GPM
HC 19-15 35.5 38.5
HC 14-10 30.0 33.0
HC 9-6 21.0 24.5
HC 6-4 16.5 20.0
MODEL FAN SPEED BASEBOARD C.I. RADIATORS
# (525 BTU/FT) (225 BTU/SQ FT)
LO-LINE HC FAN CONVECTORS — BTU/HR HEAT OUTPUT — ENTERING AIR @ 65°F
MODEL FLOW RATE POWER FAN SPEED AIR DELIVERY
#GPM
1
WATTS (CFM)
Boost 221
HC 19-15 3.0 60 Medium 179
Low 132
Boost 186
HC 14-10 3.0 60 Medium 138
Low 94
Boost 96
HC 9-6 3.0 40 Medium 69
Low 52
Boost 60
HC 6-4 3.0 25 Medium 42
Low 28
HC 19-15 0.6 3.0
HC 14-10 0.4 2.4
HC 9-6 0.4 2.3
HC 6-4 0.4 2.1
1
NOTE: Correction factor for 1.0 gpm, multiply by 0.87
ENTERING WATER TEMPERATURE (°F)
7,817 9,654 11,525 13,429 15,357 17,316 19,305 21,324 23,372 25,448
6,381 7,871 9,385 10,924 12,487 14,074 15,683 17,315 18,969 20,645
5,064 6,246 7,447 8,668 9,908 11,166 12,443 13,738 15,049 16,374
6,383 7,886 9,418 10,979 12,569 14,187 15,832 17,504 19,203 20,928
5,237 6,468 7,722 8,999 10,299 11,618 12,954 14,309 15,685 17,080
4,376 5,399 6,440 7,498 8,573 9,664 10,772 11,896 13,036 14,191
4,209 5,198 6,207 7,233 8,279 9,342 10,416 11,506 12,613 13,735
3,836 4,732 5,644 6,572 7,514 8,471 9,442 10,427 11,426 12,438
3,331 4,109 4,900 5,703 6,519 7,346 8,186 9,038 9,902 10,775
2,518 3,110 3,714 4,329 4,956 5,593 6,241 6,899 7,569 8,246
2,133 2,635 3,147 3,668 4,199 4,739 5,288 5,846 6,413 6,985
1,821 2,250 2,688 3,134 3,589 4,052 4,522 5,001 5,487 5,981
**For output at water temperatures below 140°F, optional 107°F low temperature cut-off required.
14
13
/16"
9
7
/16"
6"
3
3
/16"
2
1
/16"
Water
Connections
Pipe Entr
y
Cable Entr
y
1
7
/
7
8
/
/
"
2
9
/16"
1
11
/16"
4
5
/8"
5
1
/
2
"
A
18
1
/2"
Bottom View
Front View
Side View
110** 120** 130** 140 150 160 170 180 190 200
Heating and Cooling from a Single Convector
Lo-Line
TM
HC
Fan Unit... A highly efficient tangential
fan extends the full width of the heat
exchanger, giving extremely quiet,
trouble-free operation. All units have
aluminum fans, sealed motor bearings,
and permanently lubricated porous
bronze sleeve fan bearings.
Controls... The Lo-Line Heater Cooler has
a three speed fan, best controlled by
a 110V AC heat/cool thermostat with
3-speed sub-base. (By others.)
Heat Exchanger... Fin tube heat exchanger
is a manifold design with copper water
conduits expanded to create firm contact
with the surrounding aluminum fins.
Special air turbulator design maximizes
the rate of heat transfer. All units are
hydraulically tested to 300 psi.
Tamper-Proof Controls Cover... All units
include a tamper-proof controls cover
which conceals all electrical controls
from unauthorized usage.
Construction... The chassis is manufactured
from zinc-coated painted steel.
Water Connections…Supply and return are
1
/
2
" copper to compression isolation valves
in the lower left corner of the unit. An air
vent(s) for bleeding the convector is easily
accessed through the front of the unit with
a screwdriver. No special key is needed.
Warranty…MYSON offers a full ten year
warranty on the heat exchanger and a full
three year warranty on the fan motor.
LO-LINE HC FAN CONVECTOR SPECIFICATIONS - Engineered to be efficient.
NOTE: For
surface mounting
application only.
COOLING MODE: ENTERING WATER/AIR TEMP. DIFF. ºF
*These figures are at 50% relative humidity.
DIMENSIONS
MODEL # A
HC 19-15 45
7
8"
HC 14-10 35
7
8"
HC 9-6 25"
HC 6-4 20
1
4"
ISO 9002
L
I
S
T
E
D
NOTE: For proper sizing, use the rating at Medium or Low speeds.