Myson, Inc. • 800-698-9690 • www.MysonInc.com 13
Radiator and Fan Convector Installation
Optional Piping Arrangements
The following drawings are general examples. Consult a certified heating professional for your
specific application. MYSON recommends TRV valves on all layouts except series loop system for
maximum comfort and control of radiators. This does not apply to Fan Convectors.
MonoFlo or One Pipe System Acceptable for all MYSON
heating applications, balancing valves required.
Series Loop System Not compatible with fan
convectors. Limited to 15K btuh on panel radiators.
A single Fan Convector may be added using MonoFlo tees
as shown.
Home Run System
Two Pipe Direct Return System Acceptable
for all MYSON heating applications, balancing
valves required.
Two Pipe Reverse Return System Acceptable
for all MYSON heating applications, balancing
valves required when a Fan Convector is used
with radiators.
General information on the use of MonoFlo tees:
■ Scoop type is installed on the supply
■ Venturi type is installed on the return
■ If heating unit is below the main or more than 4
1
/
2
feet horizontally from the main, install two MonoFlo
tees with the supply arrows facing each other
Fan Convectors and Cast Iron Radiators have
different heating characteristics. Therefore, it
is recommended that the Fan Convector be on a
separate controlled heating zone.